Design, Development, Layout |
| Controlled Atmosphere Area |
| Wet Chemistry Area
A textile or leather testing laboratory will need to provide the following carefully segregated areas depending in detail on scope of operations.
Size The whole of a textile or leather laboratory does not need to have a controlled atmosphere. The area controlled should not be any larger than is necessary to accommodate the relevant functions. The bigger the area allocated the more difficult it will be to achieve the necessary control of atmospheric conditions and the more expensive the air conditioning system will be, both to buy and to operate. The maximum floor area which should be allocated to a single conditioned area is 100 square meters which, with a typical ceiling height, implies a volume of the order of 300 cubic meters. This volume will require an air conditioning system with a power of around 18 kw or 5 tons. This amount of space will be adequate for other than the largest laboratories. If more space is required to be conditioned it is recommended that a second, independent, area be set up rather than trying to condition a very large space. Functions to be Accommodated The conditioned area, typically, has to accommodate the following functions.
Key Constructional Features When designing the area which is to be conditioned to standard atmosphere the following points should be taken into account.
The best arrangement is to create the conditioned area entirely within an outer laboratory area which has conventional ventilation and air conditioning. The specialist air conditioning required for the conditioned area will then operate as ‘fine tuning’ against the general background so reducing the load. In choosing the location of the laboratory it should noted that the specialised air conditioning will be of ‘split’ type so access to an outside wall will be needed and a pathway for coolant and drain pipes. |

|
The plan shows a suggested layout for a 100 m2 square conditioned area which can be adapted to other shapes and sizes. The following points should be considered when organising fittings and services.
Air Conditioning Systems-Requirements and Control The atmosphere controlled part of the laboratory must comply with ISO 139 for textile testing and ISO 2419 for leathers. The standard atmosphere and their tolerance zone are as shown below. |

|
The 20/65 atmosphere is the one normally adopted for textile work. The alternative 23/50 should only be used if asked for by the client. In practice this will happen rarely. The atmospheres are not intended to be equivalent but simply reflect different standards. The 23/50 atmosphere is more commonly used for leather testing but 20/65 is also acceptable. Laboratories carrying out testing on both matrices will typically adopt 20/65. The conditioning and working atmosphere used should be recorded on reports of the testing. The atmospheric conditions must be monitored by traceably calibrated equipment with the minimum performance parameters shown in the table below. Note that these instruments must be independent of the air conditioning control system monitors. |
|
The air handling system must be able to control the temperature and humidity within the tolerance zone. Bearing in mind the uncertainty of measurement, this means that temperature must be controlled to within ±1.5°C and humidity to within ±2% RH of the required value if the actual tolerance or specifications are to be met. |

|
This level of control requires a specialised air conditioning system. Conventional air conditioners, whatever claims are made by suppliers, will not provide adequate control.A key issue is that the system will have to be capable of increasing humidity in the laboratory. This requires a steam generator which is not part of normal air conditioners.
This information should enable an air conditioning engineer to calculate the capacity of system needed. Providers of pre-packaged systems will typically provide a questionnaire, see below for an example, so the laboratory can list all relevant information in a convenient form. The supplier will then be able to quote for a unit of suitable capacity. |

|
Monitoring of Atmospheric Conditions The air conditioning system will normally have a readout of the temperature and humidity being achieved and will also display the settings. This readout, even if traceably calibrated, is not adequate for provision of a record of the conditions actually being achieved in the laboratory for the following reasons.
Note that wet and dry bulb systems, including whirling hygrometers, will not meet the requirements of accreditation. They have insufficient precision and cannot be calibrated to adequate uncertainty. Calibration of the thermometers in wet and dry bulb hygrometers, even if traceable, does not constitute a calibration of the humidity measurements. The temperature/humidity meter is used to monitor the atmosphere in the laboratory according to the following pattern.
Suitable example monitoring points are shown on the plan of a typical conditioned area shown above. The record of measurements must show that the required value and range of humidity and temperature is met at every monitoring point. If this is not achieved then steps must be taken to resolve the problem. Fans suitably located will often deal with locally poor air circulation.
This strategy is not recommended but if it is adopted the laboratory will have to show that, whenever testing is carried out, the correct atmospheric conditions prevailed. This will require the following measurements and records.
If at any time the temperature or humidity in the laboratory is found to be out of specification, either generally or at a particular work location, then any affected work must be suspended pending restoration of the situation. There must be a record showing the time of start and end of the suspension. Before resuming work the uniformity of the temperature and humidity must be established by carrying out the weekly test regime and recording the measurements. The entire record, of out of specification temperature/humidity and its restoration and checking, would constitute a record of non-conforming work in ISO 17025 terms. Any work inadvertently carried out when conditions did not conform must be repeated under conforming conditions. Layout and Services This area will only be required by laboratories which are conducting compositional analysis of textiles and leather and/or tests for contaminants. An example of a suitable layout for a laboratory of 50 sq metres is shown below. If the laboratory is only engaged in relatively basic tests with little instrumentation, perhaps requiring only ultra-violet spectroscopy, then no further chemical testing facilities will be required. However if more extensive instrumentation such as gas chromatographs, mass spectrometers and possibly atomic spectrometry are in use then a separate instrumental facility will be needed. |
|
In designing a wet chemistry laboratory the following points need to be considered.
Water Purifier This needs to be chosen carefully. It must generate water compatible with ISO 3696 Grade 2. The options are ion exchange, reverse osmosis and distillation. Consider the following points. |
In practice laboratories will find reverse osmosis with pre-treatment is the best option unless the feed water is of low mineralisation (<50 ppm total dissolved solids) or if there is a major water supply issue. When choosing a system it is essential that the suppliers be advised of the feed water quality and the output per day required and are asked to provide guidance on pre-treatment options and level of consumable consumption expected. For normal laboratory operations 50 to 100 litres per day will be adequate. The system should be purchased with a storage tank for half a day’s supply. Always request a booster pump for a reverse osmosis system as this will give extra speed of operation helping with high demand. If the laboratory has high purified water consumption equipment then the reverse osmosis system should be specified with the necessary capacity. Examples of such equipment are Xenon arc and other types of weathering testers and corrosion and humidity cabinets. In very poor mains water quality areas it may be necessary to treat water for use in reference washing applications so this should also be allowed for if appropriate. In general buy a reverse osmosis system with of the order of twice the capacity which you think you need at present to allow for abnormal operating situations and future expansion. Any water purification system should be fitted with an on line conductivity meter and should also be checked daily with a traceably calibrated off line meter. It is also useful to monitor pH as this can give a general indication of any change in water quality. Fume Hoods and their Applications The typical uses of the fume hood in the textile and leather testing laboratory will be to house extraction and digestion equipment. Applications will include protein determinations, wool content, the extraction of trace contaminants from leather and textiles and digestions for metals analysis. The applications should be supplied in detail to the contractor so that a hood of appropriate construction and materials is supplied. Generally speaking hoods specified for acids will be the most expensive but will be, effectively, general purpose. Hoods specified for organic solvents may not be acid resistant. Hood for work with acids should be specified with a wash down facility as this will increase their life considerably.
Fume hoods are usually manufactured to order from a list of options. Normally lighting will come as standard but you will have to specify water supply, drainage and electrical outlets. A useful standard specification is to ask for compliance with EN 14175. this covers a whole range of safety options but, crucially, the minimum face velocity to be generated as shown in the table below. This specification will effectively dictate the fan size needed to be supplied. Fans should always be located outside the laboratory so as to minimise noise. Fume hoods with no discharge to atmosphere are available. They use recirculating filters which require regular changing. Unless it is impossible to discharge to atmosphere, e.g. in a highly populated urban environment, then this type of hood is not recommended. Maintenance costs are high due to the need to change the filters and such hoods are not normally so efficient as direct discharge types. If a recirculating hood is being used then the application must be specified in detail so that appropriate filters are supplied. Separate hoods will be required for organics and acid work if maximum effectiveness of filters is to be achieved. Laboratories carrying out a large amount of extraction or distillation work involving cooling water for condensers should seriously consider having the fume cupboard supplied by a closed loop water system with a refrigerated recirculator. This will avoid the large water consumption associated with the use of normal tap water as coolant. Laboratories which only have a small amount of simple instrumentation can locate it in the main chemistry area. However if the laboratory has any instrumentation more complex than a simple colorimeter then a separate instrument room should be provided. Instruments which might be located here include chromatographs and atomic spectrometers. It is also recommended that a separate area be set aside for preparation and storage of standard solutions required for instrument calibration. One of the issues to be confronted in chemical analysis, especially at trace levels, is that the laboratory must, inevitably, have available and handle regularly, in neat form and as solutions, the very compounds being analysed. By confining the preparation of standards to a segregated area the likelihood of contamination of the parts of the laboratory where samples are handled is much reduced. The management rule should be that only the solutions actually required to calibrate instruments should leave the standards preparation room. These will normally be of high dilution so minimising the risk of contamination in the case of a spillage for example. Shown below is a suggested layout for a 50 m2 instrument facility with adjacent standard preparation room.
|
||||||||||||